Dival 507-512

Description

Direct-operated gas pressure regulator controlled by a diaphragm and contrasting regulated spring action, Dival 507-512 is suitable for use with previously filtered gaseous fluids.

Its use is strongly recommended in medium and low pressure natural gas distribution networks.

According to the European Standard EN 334, it is classified as Fail Open.

Dival 507-512 is Hydrogen Ready for NG-H2 blending.

Features

  • Accuracy class AC: up to 10 | up to 1% absolute (depending on working conditions)
  • Nominal sizes DN: 1″; 1″ 1/2
  • Lock-up pressure class SG: up to 20 (depending on version and set point)
  • Design pressure: up to 145 psig | 1 MPa for BP, up to 290.1 psig | 2 MPa for MP and TR
  • Design temperature: from -4 °F to +140 °F | from -20 °C to +60 °C
  • Connections: threaded Rp EN 10226-1, NPT ASME B1.20.1
  • Minimum differential pressure: 1.45 psig | 0.01 MPa
  • Range of downstream pressure Wd: from 6.03″ wc to 1.6 psig for BP, from 1.16 to 4.4 psig for MP, from 4.4 to 43.5 psig for TR | from 1.5 to 11 kPa for BP, from 8 to 30 kPa for MP, from 30 to 300 kPa for TR
  • Inlet pressure range: from (Pd + 1.5) psig to 145 psig | from (Pd + 0.01) MPa to 1 MPa for BP
    from (Pd + 1.5) psig to 290 psig | from (Pd + 0.01) MPa to 2 MPa for MP and TR

Documentation

Flyer

Click to download the file

Technical brochure

Click to download the file

Hydrogen compatibility declaration

Click to download the file
Scroll to top
TOP
Please turn to portrait for a better experience

Please turn to portrait
for a better experience